EasyManuals Logo

Simplex 4010 User Manual

Simplex 4010
198 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #167 background imageLoading...
Page #167 background image
A-5
Table A-5 lists the monitor point types and their descriptions.
Table A-5. Monitor Point Types
Point Type Description
FIRE Fire alarm (generic)
WATER Waterflow switch
HEAT Heat detector
DUCT Duct detector
FLAME Flame detector
PULL Pull station - manual
SMOKE Smoke detector
VSMOKE Verified smoke zone
ABORT Abort Zone (pre-signal)
EMERG Emergency Alarm
SFIRE Combination Smoke/Fire zone
VSFIRE Verified Combination Smoke/Fire zone
SPULL Combination Smoke/Pull zone
VSPULL Verified Combination Smoke/Pull zone
GENMON Generator monitor
SGENMON Supervisory generator monitor
FPUMP Fire pump monitor
SFPUMP Supervisory fire pump monitor
S2STAGE 2-stage monitor (abn=pre-signal, short=alarm)
SO Sprinkler supervision (normally open)
WSO Waterflow/sprinkler supervision (normally open)
LATSUPV Latching supervisory
SDUCT Supervisory Duct Detector
SUPDET Suppression Release detector zone
SUPABRT Suppression Release abort zone
SUPDUMP Suppression Release manual dump
SUPPRES Suppression Release pressure monitor
SUPV Supervisory (generic)
UTIL Non-alarm utility
DAMPER Damper Monitor (open/closed)
TROUBLE Trouble monitor
STYLEC Current limit = fire alarm, short/open = trouble
GVMON Generic verified monitor
Continued on next page
Software Point Types
Monitor Point Types
Device/Point T
y
pes
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010 and is the answer not in the manual?

Simplex 4010 Specifications

General IconGeneral
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
ManufacturerSimplex
Model4010
Battery Backup24 VDC
NAC Outputs4
Max Detectors250
Max Modules250
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity RangeUp to 93% RH, non-condensing