A-7
The 4010 includes two AUX relay points configured as AUX1 and AUX2. The
default point type settings for AUX1 set as an Alarm relay on until reset (point
type = RRELAY) and AUX2 set as a Trouble/Supervisory relay on until clear
(point type = TRELAY).
Table A-7 lists the Relay point types and their descriptions.
Table A-7. Relay Point Types
Point Type Description
RELAY Generic relay
PRIMARY Elevator Capture - primary
ALTERN Elevator Capture - alternate
AHUR AHU on/off relay - single relay control
AHUO AHU on relay - dual relay control
AHUF AHU off relay - dual relay control
SRELAY Alarm Relay - on ‘til silence
RRELAY Alarm relay - on 'til reset
TRELAY Trouble relay - on til clear
BRELAY Trouble relay - on til acknowledge
DHOLDER Door Holder
SWATER Waterflow relay - on ‘til silence
RWATER Waterflow relay - on ‘til reset
RSUPV Supervisory relay
SVISUAL Visual - on ‘til silence
RVISUAL Visual - on ‘til reset
SUPREL Suppression (agent discharge) release output
SIGNAL Generic Signal (no default operation)
Continued on next page
Software Point Types, Continued
Relay Point Types
Device/Point T
pes