• inhibitWaitForMaster: after expiration of the tWaitForMaster time for the
WAIT input to reset, the reclosing cycle of the slave is inhibited.
• longStartInhibit: if start pulse duration is longer than the tLongStartInh time,
the reclosing cycle is inhibited.
The ABORTED output indicates that the auto recloser is inhibited while it was in
one of following internal states:
• inProgress: auto recloser is started and dead time is in progress.
• reclaimTimeStarted: the circuit breaker closing command has started the
reclaim timer.
• wait: an auto recloser, acting as slave, is waiting for a release from the master
to proceed with its own reclosing sequence.
The SYNCFAIL output indicates that the auto recloser is inhibited because the
synchrocheck or energizing check condition has not been fulfilled within the set
time interval, tSync. The ABORTED output will also be activated.
The behavior of the functionality described above is described in Table 
177 and
Table 
178 below.
Table 177: BLKON, BLKOFF, RESET, INHIBIT and SYNC behavior when the function is in "ready" status
Output →
Input ↓
READY ACTIVE BLOCKED INHIBOUT ABORTED SYNCFAIL
None of below
inputs activated
True False False False False False
BLKON pulse False False True False False False
BLKOFF pulse True False False False False False
RESET pulse False False False False False False
INHIBIT pulse False False False True False False
SYNC True False False False False False
Table 178: BLKON, BLKOFF, RESET, INHIBIT and SYNC behavior when the function is in "in progress" status
Output →
Input ↓
READY ACTIVE BLOCKED INHIBOUT ABORTED SYNCFAIL
None of below
inputs activated
False True False False False False
BLKON pulse False False True False False False
BLKOFF pulse True False False False False False
RESET pulse False False False False False False
INHIBIT pulse False False False True True False
No SYNC False False False False True True
1MRK 505 394-UEN A Section 12
Control
Line differential protection RED650 2.2 IEC 335
Technical manual