PID-6738-SETTINGS v2
Table 357: VMMXU Non group settings (basic)
Name Values (Range) Unit Step Default Description
UL12DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
Operation Off
On
- - Off Operation Mode On / Off
UL12ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UL12Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL12Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL12RepTyp Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
-
- Cyclic Reporting type
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
UL12AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UL23DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
UL23ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UL23Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL23Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL23RepTyp Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
-
- Cyclic Reporting type
UL23AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UL31DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
UL31ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UL31Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL31Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL31RepTyp Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
-
- Cyclic Reporting type
UL31AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
Section 15 1MRK 505 394-UEN A
Monitoring
510 Line differential protection RED650 2.2 IEC
Technical manual