Table 358: VMMXU Non group settings (advanced)
Name Values (Range) Unit Step Default Description
UL12HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL12HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL12LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL12LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
100% of Ur
UL12LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
UL23HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL23HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL23LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL23LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UL23LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
UL31HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL31HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL31LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL31LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UL31LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
PID-6736-SETTINGS v3
Table 359: CMSQI Non group settings (basic)
Name
Values (Range) Unit Step Default Description
3I0DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
3I0ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
3I0Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
3I0Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
3I0RepTyp Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
-
- Cyclic Reporting type
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
3I0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
3I0AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
Operation Off
On
- - Off Operation Mode On / Off
Table continues on next page
1MRK 505 394-UEN A Section 15
Monitoring
Line differential protection RED650 2.2 IEC 511
Technical manual