EasyManua.ls Logo

ABB RED650 - Page 601

ABB RED650
926 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Z
A
pZ
L
A
U
A
I
F
R
F
(1-p).Z
L
B
Z
B
F
L
I
B
I
A
xx01000171.vsd
IEC01000171 V1 EN-US
Figure 294: Fault on transmission line fed from both ends
From figure 294 it is evident that:
U
A
I
A
p Z
L
I
F
R
F
×+× ×=
EQUATION95 V1 EN-US (Equation 78)
Where:
I
A
is the line current after the fault, that is, pre-fault current plus current change due to the fault,
I
F
is the fault current and
p
is a relative distance to the fault
The fault current is expressed in measurable quantities by:
I
F
I
FA
D
A
--------
=
EQUATION96 V1 EN-US (Equation 79)
Where:
I
FA
is the change in current at the point of measurement, IED A and
D
A
is a fault current-distribution factor, that is, the ratio between the fault current at line end A
and the total fault current.
For a single line, the value is equal to:
D
A
1 p( ) Z×
L
Z
B
+
Z
A
Z
L
Z
B
+ +
-----------------------------------------
=
EQUATION97 V1 EN-US (Equation 80)
Thus, the general fault location equation for a single line is:
1MRK 505 394-UEN A Section 15
Monitoring
Line differential protection RED650 2.2 IEC 595
Technical manual

Table of Contents

Other manuals for ABB RED650

Related product manuals