PID-6638-SETTINGS v3
Table 576: TIMESYNCHGEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
CoarseSyncSrc Off
SPA
LON
DNP
IEC103
-
- Off Coarse time synchronization source
FineSyncSource Off
SPA
LON
BIN
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
IRIG-B
GPS+IRIG-B
PPS
- - Off Fine time synchronization source
SyncMaster Off
SNTP-Server
- - Off Activate IEDas synchronization master
TimeAdjustRate Slow
Fast
- - Fast Adjust rate for time synchronization
HWSyncSrc Off
GPS
IRIG-B
PPS
-
- Off Hardware time synchronization source
SyncLostMode NoBlock
Block
BlockOnLostUTC
-
- NoBlock Behavior of dependent protection
functions when time synchronization
quality is inadequate
SyncAccLevel
Class T5 (1us)
Class T4 (4us)
Unspecified
-
- Unspecified Wanted time synchronization accuracy
CurrentSyncSource 0 - 16 - 1 - Current synchronization source
PTPGMId 0 - 16 - 1 - PTP Grand Master Id
PTPGMClass 0 - 16 - 1 - PTP Grand Master Class
PTPGMPriority1 0 - 16 - 1 - PTP Grand Master Prio 1
PTPGMPriority2 0 - 16 - 1 - PTP Grand Master Prio 2
PTPGMAccuracy 0 - 16 - 1 - PTP Grand Master Accuracy
PTPParentId 0 - 16 - 1 - PTP Id of closest parent
PTPSteps 0 - 16 - 1 - PTP number of stepsto Grand master
SNTPSource 0 - 16 - 1 - The source of the SNTP time
SNTPMaster 0 - 16 - 1 - The IP-adress of the SNTP master
GPSNumberOfSats -1 - 12 - 1 0 GPS satellites used in calculation of time
PTPOwnId 0 - 16 - 1 - PTP own clock identity