GUID-CD154442-0F80-4B69-8C43-22445FD7F865 v1
GPS settings are not supported by 650 due to hardware restrictions.
PID-6188-SETTINGS v6
Table 577: BININPUT Non group settings (basic)
Name Values (Range) Unit Step Default Description
ModulePosition 3 - 16 - 1 3 Hardware position of IO module for time
synchronization
BinaryInput 1 - 16 - 1 1 Binary input number for time
synchronization
BinDetection PositiveEdge
NegativeEdge
- - PositiveEdge Positive or negative edge detection
PID-6608-SETTINGS v4
Table 578: SNTP Non group settings (basic)
Name Values (Range) Unit Step Default Description
ServerIP-Add 0 - 18 IP
Address
1 0.0.0.0 Server IP-address
RedServIP-Add 0 - 18 IP
Address
1 0.0.0.0 Redundant server IP-address
LocalPort 0 - 65535 - 1 49152 Port number in the IED to communicate
with the SNTP server
PID-6212-SETTINGS v5
Table 579: DSTENABLE Non group settings (basic)
Name
Values (Range) Unit Step Default Description
DST Enable Off
On
- - On Enables or disables the use of Daylight
Saving Time
1MRK 505 394-UEN A Section 21
Basic IED functions
Line differential protection RED650 2.2 IEC 775
Technical manual