SMP Gateway User Manual • 189
19.3.2 Additional Failover Conditions
It is possible to define additional failover conditions to have a better control of which
SMP Gateway is active. The failover conditions are defined in the SysServerConfig.txt file and
that file can be uploaded to the SMP Gateway as any other file. In this file, 16 additional error
conditions can be defined which will force a failover. An example file was copied on your
computer’s hard drive during the SMP Tools’ installation, at the following location:
\Program Files\Cybectec\SMP Tools\Documentation\Application notes.
19.3.3 Modifying the Redundancy Settings of an Existing Group
To modify the redundancy settings of an existing group of SMP Gateways, proceed as follows:
In the SMP Gateway list, select one or both SMP Gateways of the group.
From the Redundancy menu, click Group Properties.
Modify the desired settings in the Group Properties dialog box. For a complete definition of
the settings, refer to the “Setting Up a Redundancy Group Using SMP Manager” section, page
183.
19.3.4 Ungrouping SMP Gateways
To separate 2 SMP Gateways that had been grouped together for redundancy, proceed as follows:
In the SMP Gateway list, select both SMPs.
From the Redundancy menu, click Ungroup SMP Gateways.
19.3.5 Testing and Validating the Configuration
SMP Manager displays the current state of both SMP Gateways in a redundancy group. You can
also use SMP Log and SMP Trace to display additional information.
Using SMP Log with both SMP Gateways:
Verify in the Redundancy folder that one SMP Gateway is stated as active, and that the other
one is stated as “on standby”, waiting for a failover.
For each SMP Gateway, using SMP Stats:
In the System folder, open the Redundancy folder to view additional redundancy information
and statuses.