234 SMP Gateway User Manual
Data Point Name Description
used as a failover condition.
_smp___rsLan_ok If set to 1, this binary input point indicates that the
SMP Gateway’s access to the LAN is operational. This
point’s state can be used as a failover condition.
_smp___rsVoltage_ok If set to 1, this binary input point indicates that the
SMP Gateway’s power supply’s voltage is within its normal
range of operation. This point’s state can be used as a failover
condition.
_smp___rsTemp_ok If set to 1, this binary input point indicates that the
SMP Gateway’s internal temperature is within an acceptable
range. This point’s state can be used as a failover condition.
_smp___rsMem_ok If set to 0, this binary input point indicates that the
SMP Gateway is running low on memory. This point’s state
can be used as a failover condition.
_smp___rsGroupAddress_ok If set to 0, this binary input point indicates that the public IP
address defined for the group conflicts with another device
that uses the same address. This point’s state can be used as a
failover condition.
Soft PLC
_smp___plcProgramRunning If set to 1, the binary input point indicates that a Soft PLC
automation script is currently running on the SMP Gateway.
Annunciator
_annunciator___alarmActiveCount This analog input point states the number of active alarms.
_annunciator___alarmBlocked
Count
This analog input point states the number of blocked alarms.
_annunciator___alarmConfigCount This analog input point states the number of data points
configured to trigger alarms.
_annunciator___alarmToAckCount This analog input point states the number of alarms that
require acknowledgment.
_annunciator___alarmToClear
Count
This analog input point states the number of alarms that have
been acknowledge and that may be cleared.
_annunciator___generalAlarm If set to 1, this binary input point indicates that at least one
alarm is currently active.
26.4 SMP Loader
SMP Loader should be used for the following purposes: