SMP Gateway User Manual • 83
12.2.1 Updating the Interconnections Master’s Data Point List
When the slave SMP Gateway must monitor new IEDs or more information from actual IEDs, no
update is required for the slave SMP Gateway’s Interconnections instance. This is not the case for
the master SMP Gateway, but the configuration effort is minimal.
The Interconnections master’s data point list is updated nearly the same way than it is created the
first time.
Proceed as follows:
In SMP Config, under Master Protocols, select Interconnections, and then select the master
instance.
From the Tools menu, select Import Points from File.
Select the configuration file for the slave SMP Gateway, and then click Open.
The Update Data Points dialog box will appear, listing:
points that are available and that are not actually “interconnected”;
interconnected points are no longer available on the slave SMP Gateway;
interconnected points for which the settings (ex. Scale, offset, etc.) have changed.
Using the checkboxes that are found beside every data points, select the changes you want to
apply to the master’s configuration:
Under Points to add, clear the checkboxes of points that you still do not want to be
interconnected.
If you want to keep, in the master’s configuration, points that are no longer
interconnected, clear the corresponding checkboxes under Points to remove. This may
happen if a point is temporarily unavailable on the slave SMP Gateway.
If you want the settings of modified interconnected points to remain unchanged, clear the
corresponding checkboxes under Points to modify.
Click Update to close this dialog box and to add the points to the configuration.
Save the configuration file and close SMP Config.
Send the configuration file to the SMP Gateway using SMP Manager (see “Updating the
Configuration File” on page 225).
Restart the SMP Gateway.