224 • SMP Gateway User Manual
transfers the file to your SMP Gateway and then informs you that you have to restart your
SMP Gateway for the new firmware to go into effect.
In the Restart Gateway dialog box, choose Shutdown and Restart to have the
SMP Gateway restart in normal mode.
All restarts are automatically logged in SMP Gateway’s Reset log file. If you want to,
you can type a comment in order to indicate why you restarted the SMP Gateway. This
comment will be added to the log entry.
The SMP Gateway will go through a series of startup steps, which will be displayed in the
Status column in SMP Manager. Once the startup is complete, the Status column will display
the current status of the SMP Gateway.
The Status column should display Started. If the Status column shows that your SMP Gateway
did not start up normally, refer to “Troubleshooting”, page 247.
24.3.1.2 SMP 4-20 or SMP 8-40
To update the firmware of these SMP Gateway models, you will use SMP Loader. You will find
detailed instructions on under “SMP Loader”, page 234.
Exec
ute the steps in the order presented here:
Update the primary and secondary bootstrap programs.
Update the resident diagnostics.
Update Windows CE.
Remove the cable that you connected between the SMP Gateway console port and your PC
when you used SMP Loader.
Reset the SMP Gateway by holding down the reset button for at least 5 seconds, until the 4
front panel LEDs turn amber.
Start SMP Manager.
The SMP Gateway will go through a series of startup steps, which will be displayed in the Status
column. Once the startup is complete, the Status column should display Started. If the Status
column shows that your SMP Gateway did not start up normally, refer to “Troubleshooting”, page
247.
24.3.2 Updating the SMP Gateway Application
You will now update the SMP Gateway application.
Proceed as follows:
In the SMP Manager window, click your SMP Gateway.
From the Update menu, click Update SMP Gateway Application.
The Select Library dialog box appears.