Chapter 6 Description of Function Codes
6.1 Basic ParametersGroup P0
P0.00 Control Mode Setting Range02 0
0V/F ControlIt is applicable to applications with low load requirements or applications
where one AC drive operates multiple motors, such as fan and pump.
1Sensorless flux vector control (SFVC) It indicates open-loop vector control, and is
applicable to high-performance control applications such as machine tool, centrifuge, wire
drawing machine and injection molding machine. One AC drive can operate only one motor.
2Closed-loop vector control(CLVC)It is applicable to high-accuracy speed control or
torque control applications such as high-speed paper making machine, crane and elevator.
One AC drive can operate only one motor. An encoder must be installed at the motor side,
and a PG card matching the encoder must be installed at the AC drive side.
P0.01
Main frequency source 1
selection
Setting Range09 0
0Digital setting (non-retentive at power failure)You can change the set frequency by
pressing
▲and▼on the operation panel. When the AC drive is powered on again after power
failure, the set frequency reverts to the value of P0.02 .
1Digital setting (retentive at power failure)You can change the set frequency by
pressing keys
▲and▼on the operation panel (or using the UP/DOWN functions of input
terminals).When the AC drive is powered on again after power failure, the set frequency
is the value memorized at the moment of the last power failure.
2VI analog setting(VI-GND). 0–10 V voltage input
3CI analog setting (CI-GND). 0–10 V voltage input or 4–20 mA current input, determined