Chapter 6 Description of Function Codes
6.1 Basic Parameters(Group P0)
P0.00 Control Mode Setting Range:0~2 0
0:V/F Control:It is applicable to applications with low load requirements or applications
where one AC drive operates multiple motors, such as fan and pump.
1:Sensorless flux vector control (SFVC) :It indicates open-loop vector control, and is
applicable to high-performance control applications such as machine tool, centrifuge, wire
drawing machine and injection molding machine. One AC drive can operate only one motor.
2:Closed-loop vector control(CLVC):It is applicable to high-accuracy speed control or
torque control applications such as high-speed paper making machine, crane and elevator.
One AC drive can operate only one motor. An encoder must be installed at the motor side,
and a PG card matching the encoder must be installed at the AC drive side.
P0.01
Main frequency source 1
selection
Setting Range:0~9 0
0:Digital setting (non-retentive at power failure):You can change the set frequency by
pressing
▲
▲and▼on the operation panel. When the AC drive is powered on again after power
failure, the set frequency reverts to the value of P0.02 .
1:Digital setting (retentive at power failure):You can change the set frequency by
pressing keys
▲
▲and▼on the operation panel (or using the UP/DOWN functions of input
terminals).When the AC drive is powered on again after power failure, the set frequency
is the value memorized at the moment of the last power failure.
2:VI analog setting(VI-GND). 0–10 V voltage input
3:CI analog setting (CI-GND). 0–10 V voltage input or 4–20 mA current input, determined