152
temperature is lower than 40°C.
If this parameter is set to 1, the cooling fan keeps working after
power-on.
P2.47
Wakeup frequency
Setting Range
Dormant
frequencyP2.49P0.05
0.00Hz
P2.48
Wakeup delay time
Setting Range
0.0s6500.0s
0.0s
P2.49
Dormant frequency
Setting Range
0.00HzWakeup
frequencyP2.47)
0
P2.50
Dormant delay time
Setting Range
0.0s6500.0s
0.0s
These parameters are used to implement the dormant and wakeup functions in the water
supply application.
When the AC drive is in running state, the AC drive enters the dormant state and stops
automatically after the dormant delay time (P2.50) if the set frequency is lower than or equal
to the dormant frequency (P2.49).
When the AC drive is in dormant state and the current running command is effective, the AC
drives starts up after the wakeup delay time (P2.48) if the set frequency is higher than or
equal to the wakeup frequency (P2.47).
Generally, set the wakeup frequency equal to or higher than the dormant frequency. If the
wakeup frequency and dormant frequency are set to 0, the dormant and wakeup functions