1 : Switchover between operation panel control and remote command control. You can
perform switchover from the current command source to the operation panel control (local
operation).
If the current command source(P0.03 ) is operation panel control, this key is invalid.。
2:Switchover between forward rotation and reverse rotation:You can change the direction
of the frequency reference by using the REV key.
It is valid only when the current command source is operation panel control.
3:Forward JOG:You can perform forward JOG (FJOG) by using the REV key.
4:Reverse JOG: You can perform reverse JOG (FJOG) by using the REV
key.
P7.01
STOP key function
Setting Range:0~1 0
0:STOP key enabled only in operation panel control.
1:STOP key enabled in any operation mode.
P7.02
LED display running parameter
1
Setting Range:
0x 0000 ~0x FFFF
0x1F
P7.03
LED display running parameter
2
Setting Range:
0x 0000 ~0x FFFF
0x00
These two parameters are used to set the parameters that can be viewed when the AC
drive is in the running state. You can view a maximum of 32 running state parameters that
are displayed from the lowest bit of P7.02.