1 Switchover between operation panel control and remote command control. You can
perform switchover from the current command source to the operation panel control (local
operation).
If the current command sourceP0.03 is operation panel control, this key is invalid.
2Switchover between forward rotation and reverse rotationYou can change the direction
of the frequency reference by using the REV key.
It is valid only when the current command source is operation panel control.
3Forward JOGYou can perform forward JOG (FJOG) by using the REV key.
4Reverse JOG: You can perform reverse JOG (FJOG) by using the REV
key.
P7.01
STOP key function
Setting Range01 0
0STOP key enabled only in operation panel control.
1STOP key enabled in any operation mode.
P7.02
LED display running parameter
1
Setting Range
0x 0000 ~0x FFFF
0x1F
P7.03
LED display running parameter
2
Setting Range
0x 0000 ~0x FFFF
0x00
These two parameters are used to set the parameters that can be viewed when the AC
drive is in the running state. You can view a maximum of 32 running state parameters that
are displayed from the lowest bit of P7.02.