P3.42 X valid mode
Selection 2
Setting Range:
00000~11111
00000
P3.43 AI as valid status selection of X Setting Range:000~
111
000
0:High level valid, 1:Low level valid.
These parameters are used to set the valid mode of X terminals.
The X terminal is valid when being connected with COM, and invalid when being
disconnected from COM.
The X terminal is invalid when being connected with COM, and invalid when being
disconnected from COM.
P3.41 control terminal description: Unit’s digit :X1,Ten’s digit:X 2,Hundred’s digit:X
3,Thousand’s digit:X 4,Ten thousand’s digit:X 5。
P3.42 control terminal description:Unit’s digit:X6,Ten’s digit:X 7,Hundred’s digit:X
8,Thousand’s digit:X9,Ten thousand’s digit:X10
P3.43 control terminal description:VI, CI.
6.5
Output Terminals(Group P4)
P4.00
FM terminal output mode
Setting Range:0~1 0
0:Pulse output (FMP);1:Switch signal output (FMR)
The FM terminal is programmable multiplexing terminal. It can be
used for high-speed pulse output (FMP), with maximum
frequency of 100 kHz. Refer to P4.06 for relevant functions of
FMP. It can also be used as open collector switch signal output