EasyManua.ls Logo

degdrive DGI900 - Standard Function Parameters; Chapter 5 Function Code Table

degdrive DGI900
251 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
60
Chapter 5 Function Code Table
5.1 The symbols in the function code table are described as follows
“○”: The parameter can be modified when the AC drive is in either stop or running state.
“×”: The parameter can not be modified when the AC drive is in the running state.
“* ”: The parameter is factory parameter and can not be modified.
5.2 Standard Function Parameters
Group P0: Standard Function Parameter
Function
Code
Parameter Name Setting Range Minimum
Unit
Default Propert
y
P0.00 Control mode 0V/F control
1Sensorless vector
control(SVC)
2Sensor vector control
1
0 ×
P0.01 Main frequency
source 1 selection
0Digital setting
1(P0.02UP/DOWN can
modify,non-retentive at power
failure)
1Digital setting
2(P0.02UP/DOWN can
modify,retentive at power
failure)
2VI analog settingVI-
GND
3: CIanalog settingCI-
1 0 ×

Table of Contents