60
Chapter 5 Function Code Table
5.1 The symbols in the function code table are described as follows
“○”: The parameter can be modified when the AC drive is in either stop or running state.
“×”: The parameter can not be modified when the AC drive is in the running state.
“* ”: The parameter is factory parameter and can not be modified.
5.2 Standard Function Parameters
Group P0: Standard Function Parameter
Function
Code
Parameter Name Setting Range Minimum
Unit
Default Propert
y
P0.00 Control mode 0:V/F control
1:Sensorless vector
control(SVC)
2:Sensor vector control
1
0 ×
P0.01 Main frequency
source 1 selection
0:Digital setting
1(P0.02,UP/DOWN can
modify,non-retentive at power
failure)
1:Digital setting
2(P0.02,UP/DOWN can
modify,retentive at power
failure)
2:VI analog setting(VI-
GND)
3: CIanalog setting(CI-
1 0 ×