177
The output pulse frequency of the FMP terminal ranges from 0.01 kHz to "Maximum FMP
output frequency" (P5.09). The value of P5.09 is between 0.01 kHz and 100.00 kHz.
The output range of AO1 and AO2 is 0–10 V or 0–20 mA.
The relationship between pulse and analog output ranges and
corresponding functions is listed in the following table.
Value Function Range (Corresponding to Pulse or Analog
Output Range 0.0%–100.0%)
0 Running frequency 0 to maximum output frequency
1 Set frequency 0 to maximum output frequency
2 Output current 02 times of rated motor current
3 Output current 0.0A1000.0A
4 Output torque (absolute
value)
0 to 2 times of rated motor torque
5 Output torque (actual
value)
-2 times of rated motor torque to 2 times of rated
motor torque
6 Output voltage 01.2 times of rated AC drive voltage
7 Output voltage 0.0V1000.0V
8 Motor rotational speed 0 to rotational speed corresponding to
maximum output frequency
9 Output power 02 times of rated power
10 VI input 010V
11 CI input 010Vor 420mA
12 Pulse input 0.01kHz100.00kHz
13 Communication setting 0.0%100.0%
14 Length 0 to maximum set length