action selection 4 00000~22222
PA.43 、PA.44、PA.35 and PA.36 are used to stop the AC drive when fault occurs, setting
range, 0:Coast to stop;1:Stop according to the stop mode;2:Continue to run.
PA.43 Fault protection action selection 1
Unit's digit : Motor overload(E-11); Ten's digit: Power input phase loss(E-12) ; Hundred's
digit: External equipment fault (E-15);Thousand's digit:Communication fault (E-16);Ten
thousand's digit:EEPROM read-write fault (E-17)
PA.44 Fault protection action selection 2
Unit's digit:Power input phase loss (E-19);Ten's digit:Encoder fault (E-21);Hundred's
digit : Accumulative running time reached (E-23) ; Thousand's digit : 上 Accumulative
power-on time reached (E-24);Ten thousand's digit:Motor overheat (E-27)
PA.45 Fault protection action selection 3
Unit's digit:Too large speed deviation (E-28) 1;Ten's digit:Motor over-speed (E-29)2;
Hundred's digit:Load becoming 0;Thousand's digit: PID feedback lost during running(E-
34);Ten thousand's digit: Reserved
PA.46 Fault protection action selection 4
Unit's digit : User-defined fault 1 (E-32) ; Ten's digit : User-
defined fault 2(E-33)
PA.50
Frequency selection for
continuing to run upon fault
Setting Range:0~4 0
0 : Current running frequency ; 1 : Set frequency ; 2 : Frequency upper limit ; 3:
Frequency lower limit;4: Backup frequency upon abnormality