action selection 4 00000~22222
PA.43 PA.44PA.35 and PA.36 are used to stop the AC drive when fault occurs, setting
range, 0Coast to stop1Stop according to the stop mode2Continue to run.
PA.43 Fault protection action selection 1
Unit's digit Motor overload(E-11); Ten's digit: Power input phase loss(E-12) Hundred's
digit: External equipment fault (E-15)Thousand's digitCommunication fault (E-16)Ten
thousand's digitEEPROM read-write fault (E-17)
PA.44 Fault protection action selection 2
Unit's digitPower input phase loss (E-19)Ten's digitEncoder fault (E-21)Hundred's
digit Accumulative running time reached (E-23) Thousand's digit Accumulative
power-on time reached (E-24)Ten thousand's digitMotor overheat (E-27)
PA.45 Fault protection action selection 3
Unit's digitToo large speed deviation (E-28) 1Ten's digitMotor over-speed (E-292
Hundred's digitLoad becoming 0Thousand's digit PID feedback lost during running(E-
34)Ten thousand's digit: Reserved
PA.46 Fault protection action selection 4
Unit's digit User-defined fault 1 (E-32) Ten's digit User-
defined fault 2(E-33)
PA.50
Frequency selection for
continuing to run upon fault
Setting Range0~4 0
0 Current running frequency 1 Set frequency 2 Frequency upper limit 3:
Frequency lower limit4: Backup frequency upon abnormality