P4.15
Relay1 output delay time
Setting Range:0.0s~3600.0s 0.0s
P4.16
Relay2 output delay time
Setting Range:0.0s~3600.0s 0.0s
P4.17
DO1 output delay time
Setting Range:0.0s~3600.0s 0.0s
P4.18
DO2 output delay time
Setting Range:0.0s~3600.0s 0.0s
These parameters are used to set the delay time of output
terminals FM, relay 1, relay 2, DO1 and DO2 from status change
to actual output.
P4.19
DO valid mode selection
Setting Range:00000~11111 00000
It is used to set the logic of output terminals FM, relay 1, relay 2, DO1 and DO2.
Unit's digit: FM valid mode;Ten's digit: Relay 1 valid mode;Hundred's digit: Relay 2 valid
mode;Thousand's digit: DO1 valid mode;Ten thousand's digit:DO2 valid mode.
0: Positive logic,The output terminal is valid when being connected with COM, and invalid
when being disconnected from COM.
1:Positive logic,The output terminal is invalid when being connected with COM, and valid
when being disconnected from COM.
6.6 V/F Control Parameter(Group P5)
P5.00
V/F curve setting
Setting Range:00~11 00
According to the different load requirements, there are five kinds of curve modes can be
selected base on P5.00 setting.
0:Linear V/F:It is applicable to common constant torque load.
1:Multi-point V/F:It is applicable to special load such as dehydrator and centrifuge. Any
such V/F curve can be obtained by setting parameters of PA.01 to PA.06.