If a fault occurs during the running of the AC drive and the handling of fault is set to
"Continue to run", the AC drive displays A-** and continues to run at the frequency set in
PA.50.
Note:
(**)content is confirmed by fault,for example if the fault is Power
input phase loss (E-12), then the ac drive display A-12.
PA.51
Backup frequency upon
abnormality
Setting Range:60%~100% 100%
The setting of PA.51
is a percentage relative to the maximum
frequency.
PA.53
Motor overheat protection
threshold
Setting Range:
0℃~200℃
110℃
PA.54
Motor overheat warning
threshold
Setting Range:
0℃~200℃
90℃
PA.55 Action selection at instantaneous
power failure
Setting Range: 0~2 0
PA.56 Action pause judging voltage at
instantaneous power failure
Setting Range:
80%~100%
90
PA.57 Voltage rally judging time at
instantaneous power failure
Setting Range:
0.00s~100.00s
0.5S
PA.58 Action judging voltage at
instantaneous power failure
Setting Range:
60%~100%
80