If terminal JOG is preferred, the AC drive switches to terminal
JOG running state when there is a terminal JOG command during
the running process of the AC drive.
P2.26
Frequency detection value
(FDT2)
Setting Range:0.00Hz~
maximum frequency
50.00Hz
P2.27
Frequency detection
hysteresis (FDT2)
0.0%~100.0% 0.5%
The frequency detection function is the same as FDT1 function.
For details, refer to the descriptions of P2.20 and P2.21.
P2.28
Any frequency reaching
detection value 1
Setting Range:0.00Hz~
maximum frequency
0.00Hz
P2.29
Any frequency reaching
detection amplitude 1
Setting Range:
0.0%~100.0%
0.0%
P2.30 Any frequency reaching
detection value 2
Setting Range:0.00Hz~
maximum frequency
50.00Hz
P2.31
Any frequency reaching
detection amplitude 2
Setting Range:
0.0%~100.0%
0.0%
If the output frequency of the AC drive is within the positive and
negative amplitudes of the any frequency reaching detection
value, the corresponding DO becomes ON.
P2.32
Zero current detection
level
Setting Range:
0.0%~300.0%
5.0%
P2.33
Zero current detection
delay time
Setting Range:
0.01s~600.00s
0.10s
If the output current of the AC drive is equal to or less than the zero current detection level