If the overcurrent stall gain is set to 0, the overcurrent stall
function is disabled.
PA.09 Fault auto reset times Setting Range0~20 0
PA.10 DO action during fault auto reset Setting Range0~1 1
PA.11 Time interval of fault auto reset Setting Range0.1s~100.0s 1.0s
It is used to set the times of fault auto resets if this function (PA.09) is used. After the value
is exceeded, the AC drive will remain in the fault state.
It is used to decide whether the DO acts during the fault auto reset if the fault auto reset
function is selected, you can set by PA.10.
0Not act
1Act
PA.11 used to set the waiting time from the alarm of the AC drive
to fault auto reset.
PA.12 Input phase loss
protection/contactor energizing
protection selection
Setting Range00~11 11
Unit's digit: Input phase loss protection 0Disabled; 1Enabled
Ten's digit: Contactor energizing protection 0Disabled; 1Enabled
PA.13 Output phase loss protection
selection
Setting Range0~1 1