If a resolver is applied, set the number of pole pairs properly.
P8.37 Auto-tuning selection Setting Range: 0~2 0
0:No auto-tuning
1:Asynchronous motor static auto-tuning
It is applicable to scenarios where complete auto-tuning cannot be performed because the
asynchronous motor cannot be disconnected from the load.
Before performing static auto-tuning, properly set the motor type and motor nameplate
parameters of P8.00 to P8.05 first. The AC drive will obtain parameters of P8.06 to P8.08 by
static auto-tuning.
Set this parameter to 1, and press FWD. Then, the AC drive starts static auto-tuning.
2:Asynchronous motor complete auto-tuning
To perform this type of auto-tuning, ensure that the motor is disconnected from the load.
During the process of complete auto-tuning, the AC drive performs static auto-tuning first
and then accelerates to 80% of the rated motor frequency within the acceleration time set in
P0.12. The AC drive keeps running for a certain period and then decelerates to stop within
deceleration time set in P0.13.
Before performing complete auto-tuning, properly set the motor type, motor nameplate
parameters of P8.00 to P8.05, "Encoder type" (P8.27) and "Encoder pulses per revolution"
(P8.28) first.
The AC drive will obtain motor parameters of P8.06 to P8.10, "A/B phase sequence of ABZ
incremental encoder" (P8.30) and vector control current loop PI parameters of P8.14 to
P8.17 by complete auto-tuning.