4) Send a voltage signal (approximately 8 V) to AI.
5) Measure AI voltage and save it to PF.03.
6) View the displayed value of b0.21 and save the value to
PF.04.
PF.04 CI measured voltage 1 Setting Range:
0.500 V~4.000 V
Factory-corrected
PF.05 CI displayed voltage 1 Setting Range:
0.500 V~4.000 V
Factory-corrected
PF.06 CI measured voltage 2 Setting Range:
6.000V~9.999V
Factory-corrected
PF.07 CI displayed voltage 2 Setting Range:
6.000V~9.999V
Factory-corrected
These parameter corrected method is the same with PF.00 to
PF.03, view the displayed value of b0.22.
PF.12 AO1 target voltage 1 Setting Range:
0.500 V~4.000 V
Factory-corrected
PF.13 AO1 measured voltage 1 Setting Range:
0.500 V~4.000 V
Factory-corrected
PF.14 AO1 target voltage 2 Setting Range:
6.000V~9.999V
Factory-corrected
PF.15 AO1 measured voltage 2 Setting Range:
6.000V~9.999V
Factory-corrected
These parameters are used to correct the AO