193
with function 38 "PID integral pause" is ON or not.
Ten's digit Whether to stop integral operation when the output reaches the limit 0
Continue integral operation1Stop integral operation.
If "Stop integral operation" is selected, the PID integral operation
stops, which may help to reduce the PID overshoot.
P6.26 Detection value of PID
feedback loss
Setting Range 0.1%
100.0%
0.0%
P6.27 Detection time of PID
feedback loss
Setting Range0.0s
20.0s
1s
These parameters are used to judge whether PID feedback is
lost. Not judging feedback loss when set P6.26 to 0.0%.
If the PID feedback is smaller than the value of P6.26 and the
lasting time exceeds the value of P6.27, the AC drive reports
Err31 and acts according to the selected fault protection action.
P6.28 PID operation at stop Setting Range01 0
0No PID operation at stop1PID operation at stop
It is used to select whether to continue PID operation in the state of stop. Generally, the PID
operation stops when the AC drive stops.
6.8 Operation Panel and DisplayGroup P7
P7.00
REV key function selection
Setting Range04 3
0REV key disabled