79
P3.43 AI as valid status
selection of DI
0:High level valid
1:Low level valid
Unit’s digit:VI
Ten’s digit:CI
111 111 ×
Group P4: Output Terminals
Function
Code
Parameter
Name
Setting Range Minimum
Unit
Default Property
P4.00 FM terminal
output mode
0:Pulse output (FMP)
1:Switch signal
output(FMR)
1 0 ○
P4.01 FM
function(open-
collector output
terminal)
0:No output
1:AC drive running
2:Fault output (stop)
3:Frequency-level detection
FDT1 output
4:Frequency reached
5:Zero-speed running(no
output at stop)
6:Motor overload pre-
warning
7:AC drive overload pre-
warning
8:Set count value reached
9:Designated count value
reached
1 0 ○
P4.02 Relay function
T/A-T/B-T/C
1 2 ○
P4.03 Extension card
relay
function(R/A-
R/B-R/C)
1 0 ○
P4.04 DO1 function
selection
(Reserved)
1 1 ○

Table of Contents