After this terminal becomes ON, the AC drive directly switches over to the DC braking state.
33Normally closed (NC) input of external fault
34Frequency modification forbidden
After this terminal becomes ON, the AC drive does not respond to any frequency
modification.
35Reverse PID action direction
After this terminal becomes ON, the PID action direction is reversed to the direction set in
P6.03.
36External STOP terminal 1
In operation panel mode, this terminal can be used to stop the AC drive, equivalent to the
function of the STOP key on the operation panel.
37Command source switchover terminal 2
It is used to perform switchover between terminal control and communication control. If the
command source is terminal control, the system will switch over to communication control
after this terminal becomes ON.
38PID integral pause
After this terminal becomes ON, the integral adjustment function pauses. However, the
proportional and differentiation adjustment functions are still valid.
39Switchover between main frequency source X and preset frequency
After this terminal becomes ON, the frequency source X is replaced by the preset frequency
set in P0.02.