139
P2.07
Acceleration time 4
Setting Range0.16000.0 20.0
P2.08
Deceleration time 4
Setting Range0.16000.0 20.0
The DGI900 provides a total of four groups of
acceleration/deceleration time, and you can switch over between
the four groups of acceleration/deceleration time through different
state combinations of terminals. For more details, see the
descriptions of P3.00P3.09.
P2.09
Jump frequency 1
Setting Range0.00500.00Hz 0.00Hz
P2.10
Jump frequency 2
Setting Range0.00500.00Hz 0.00Hz
P2.11
Jump frequency amplitude
Setting Range0.0030.00Hz 0.00Hz
If the set frequency is within the frequency jump range, the actual running frequency is the
jump frequency close to the set frequency. Setting the jump frequency helps to avoid the
mechanical resonance point of the load.
The DGI900 supports two jump frequencies. If both are set to 0, the frequency jump function
is disabled. The principle of the jump frequencies and jump amplitude is shown in the
following figure 6-6.