If the output frequency of the AC drive is 0, the terminal becomes ON. In the state of stop,
the signal is still ON.
24:Accumulative power-on time reached
If the AC drive accumulative power-on time exceeds the value set in P2.17, the terminal
becomes ON.
25:Frequency level detection FDT2 output:Refer to the descriptions of P2.26 and P2.27.
26:Frequency 1 reached:Refer to the descriptions of P2.28 and P2.29.
27:Frequency 2 reached:Refer to the descriptions of P2.30 and P2.31.
28 : Current 1 reached : Refer to the descriptions of P2.36 and P2.37. 29 : Current 2
reached:Refer to the descriptions of P2.38 and P2.39.
30:Timing reached
If the timing function (P2.40) is valid, the terminal becomes ON after the current running
time of the AC drive reaches the set time(P2.42).
31:VI input limit exceeded
If VI input is larger than the value of P2.44(VI input voltage upper limit) or lower than the
value of P2.43 (VI input voltage lower limit), the terminal becomes ON.
32:Load becoming 0:
If the load becomes 0, the terminal becomes ON.
33:Reverse running:
If the AC drive is in the reverse running state, the terminal becomes ON.