Grid voltage is low Check grid voltage
E-12 Output lack
phases
Cable between Inverter and
motor is fault
Check the peripheral fault
Output 3-phases un balance Check motor 3 phases winding
Drive board fault Contact supplier
IGBT module fault Contact supplier
Control board connecting wire
or plug-in unit loose
Check and re-wiring
E-13 Peripheral
fault
External fault terminals closed Check the reason
E-14 Current
detecting
circuit fault
Loose wiring or terminal
connections
Check and re-wiring
Auxiliary power source
damaged
Contact supplier
Hall component damaged Contact supplier
Amplifier circuit abnormal Contact supplier
E-15 RS232/485
Communicatio
n fault
Baud rate setting incorrect Set baud rate properly
Serial port communication fault Press Key to reset or contact
supplier
Improper fault alarm parameter
setting
Revise function code PC group