P3.08 X9 function
selection
Reserved 1 0 ×
P3.09 X10 function
selection
Reserved 1 0 ×
P3.10 VI function
selection(DI)
0~59 1 1 ×
P3.11 CI function
selection(DI)
0~59 1 1 ×
P3.13 Terminal filter time 0.000S~1.000S 1 0.010S ×
P3.14 Terminal command
mode
0:Two-line mode 1
1:Two-line mode 2
2:Three –line mode 1
3:Three –line mode 2
0 0 ○
P3.15 Terminal
UP/DOWN rate
0.001HZ/S ~ 65.535HZ/S 0.001Hz/s 1.00HZ/
S
○
P3.16 VI minimum input 0.00V ~ P3.15 1 0.00V ○
P3.17 Corresponding
setting of VI
minimum input
-100.0% ~ +100.0% 1 0.0% ○
P3.18 VI maximum input P3.13 ~ +10.00V 0.01V 10.00V ○
P3.19 Corresponding
setting of VI
maximum input
-100.0% ~ +100.0% 0.01Hz 100.0% ○
P3.20 VI filter time 0.00S ~ 10.00S 0.01S 0.10S ○
P3.21 CI minimum input 0.00V ~ P3.20 0.01V 0.00V ○
P3.22 Corresponding
setting ofCI
-100.0% ~ +100.0% 0.1% 0.0% ○