99
gain
PA.06 Over current stall
protective
current
100%~200% 150% ○
PA.07 Short-circuit to
ground upon
power-on
0:Disabled
1:Enabled
1 ○
PA.09 Fault auto reset
times
0~20 0 ○
PA.10 DO action during
fault auto reset
0:Not act
1:Act
0 ○
PA.11 Time interval of
fault auto reset
0.1s~100.0s 1.0s ○
PA.12 Input phase loss
protection/contac
tor energizing
Unit’s digit:Input phase loss
protection
Ten’s digit:Contactor
energizing protection
0:Disabled
1:Enabled
11 ○
PA.13 Output phase
loss protection
selection
0:Disabled
1:Enabled
1 ○
PA.14 1st fault type 0:No fault
1:Over current during
- - *
PA.15 2nd fault type - - *

Table of Contents