AH500 Module Manual
9-14
#683
Packed single-point information with status change detection corresponds
to the starting position of D device
#684 Measured value, normalized value without quality descriptor corresponds
to the starting position of D device
Example: when AH15EN-5A is as a master, it will scan and obtain the IOA of the remote
device. Create type ids to correspond to the CPU registers as the starting position for
data mapping and the obtained value will be stored to the specific register. Users can
input the values according to the table below and trigger to create. Take Single-point
information as an example: IOA100 corresponds to M100, IOA101 and M101 and so on.
The same rule applies to 2
nd
~ 16
th
remote devices. Refer to section 9.3.5 for details on
type id parameters and codes.
CR
Number
Value
in the
control
register
Description
#672 100
Single-point information corresponds to the starting position
from M100
#673 200 Double-point information corresponds to the starting position
from M200
#674 300
Step position information corresponds to the starting position
from D300
#675 400 Bitstring of 32 bit corresponds to the starting position from
D400
#676 500 Measured value, normalized value corresponds to the starting
position from D500
#677 600
Measured value, scaled value corresponds to the starting
position from D600
#678 700 Measured value, short floating point value corresponds to the
starting position from D700
#679 800 Integrated totals corresponds to the starting position from
D800
#680 900
Event of protection equipment corresponds to the starting
position from D900
#681 1000 Packed start events of protection equipment corresponds to
the starting position from D1000
#682 1100 Packed output circuit information of protection equipment
corresponds to the starting position from D1100
#683 1200
Packed single-point information with status change detection
corresponds to the starting position from D1200
#684 1300 Measured value, normalized value without quality descriptor
corresponds to the starting position from D1300