Chapter 10 DeviceNet Communication Module AH10DNET 
10-61 
Indication  How to deal with
OFF
Green 
light ON 
Duplicate ID 
detection has not 
completed. 
Ensure that at least one node and 
AH10DNET-5A have the same baud rate 
and communicate normally on the network. 
Red light 
ON 
Green 
light ON
detection failed or 
bus-off.
 
1. Ensure that the node address of 
AH10DNET-5A is unique. 
2. Repower it. 
Red light 
ON
Red light 
blinking   
No network power 
1. Check if the network cable connection is 
correct. 
2. Check if the network power is normal. 
ON 
ON
Hardware error  Return it to the factory for repair. 
10.10.2  Seven-segment Display Diagnosis 
0~63 
Node address of DVPDNET-SL 
(in normal operation)
 
-- 
80 
AH10DNET-5A in STOP status. 
Turn the AH500 series CPU module to RUN 
and start I/O data exchange. 
F0 
AH10DNET-5A is identical to 
that of other node or exceeds 
the valid range.
 
1.  Ensure that the node address of 
AH10DNET-5A is unique. 
2.  Repower it after changing its node address. 
F1 
No slave device is configured in 
the scan list of AH10DNET-5A
 
Configure the slave in the scan list and 
download the scan list to AH10DNET-5A. 
F2 
Excessively low voltage for 
AH10DNET-5A 
Check if the power supply for AH10DNET-5A 
and the AH500 series CPU module is normal. 
F3 
Entering test mode 
Switch IN1 from ON to OFF and repower 
AH10DNET-5A. 
F4 
Bus-off 
1. Check if the network cable is normal and the 
shielded wire has been grounded. 
2. Check if the baud rates of all node equipment 
on the network are consistent. 
3. Check if both of the two ends of the network 
have a 121 Ω resistor. 
4. Repower AH10DNET-5A.
 
F5 
No network power 
Make sure the cable is correctly connected and 
check if the network power is normal. 
F6 
Internal errors; internal memory 
unit errors
 
If the error still exists after power on again, send 
your AH10DNET-5A back to the factory for 
repair. 
F7 
Data exchange unit errors 
If the error still exists after power on again, send 
your AH10DNET-5A back to the factory for 
repair. 
F8 
Sequence number detection 
errors
 
If the error still exists after power on again, send 
your AH10DNET-5A back to the factory for 
repair. 
F9 
An error in reading/writing the 
configuration data.
 
If the error still exists after power on again, send 
your AH10DNET-5A back to the factory for 
repair. 
FA 
AH10DNET-5A is the same as 
that of the slave configured in 
the scan list.
 
Method 1: Reset the node address of 
AH10DNET-5A, which must be different from 
that of the slave configured in the scan list and 
then repower it.