AH500 Module Manual
12-36
Select “<Slot 2> 2 Word Out 2 Word In” in the box marked in red and then double click the place
marked in blue as below so as to set the starting addresses for input and output of the configured
module.
Input mapping
(slave->master)
The initial number of the D
registers in the slave PLC (The
register is for sending data to the
master)
D500
Output mapping
(master->slave)
The initial number for the D
registers in the slave PLC (The
register is for receiving data that
the master transmits).
D600
Note: the initial D register No. of each configured module must be set up separately.
Click “Signal Configuration” on the left-side window and then the detailed information about the
configured module appears on the right-side window. The input and output data lengths of
configured module on the above window can be seen from the following window.
The configured module of the slave corresponds to the mapping parameter of the slave as follows.
Configured module of slave
Mapping parameter of slave
4 Word Out, 4 Word In