AH500 Module Manual 
13-34 
(Slave->Master) 
The number of starting D 
register in input area 
0 ( Changeable by the keyboard) 
(Master->Slave) 
The number of starting D 
register in output area 
100 (Changeable by the keyboard) 
 
 
7.  Double click AH10PFBS-5A icon on the PROFIBUS network in “HW Config” dialog box and 
then the following window pops up. 
 
 
The indication of the above option is shown below. 
Los comm. 
with master 
Hold I/O data 
The input and output data before offline will keep 
unchanged when AH10PFBS-5A and the master 
are offline (E.g. the PROFIBUS-DP bus connector 
is removed from the slave). 
Clear I/O data 
The output data received from the master will be 
cleared to 0 and the input data will keep 
unchanged when AH10PFBS-5A and the master 
are offline (E.g. the PROFIBUS-DP bus connector 
is removed from the slave). 
 
8.  Download the configuration data after configuration of the data is over.   
After the connection between the master and AH10PFBS-5A is made and the NET light of 
AH10PFBS-5A is green, it indicates that the communication between AH10PFBS-5A and 
the PROFIBUS-DP master is normal. Otherwise, shoot the trouble according to the 
instruction in chapter 8.