AH500 Module Manual
13-34
Item
Indication
Default
Input D mapping
(Slave->Master)
The number of starting D
register in input area
0 ( Changeable by the keyboard)
output D mapping
(Master->Slave)
The number of starting D
register in output area
100 (Changeable by the keyboard)
7. Double click AH10PFBS-5A icon on the PROFIBUS network in “HW Config” dialog box and
then the following window pops up.
The indication of the above option is shown below.
Option
Selection
Indication
Los comm.
with master
Hold I/O data
The input and output data before offline will keep
unchanged when AH10PFBS-5A and the master
are offline (E.g. the PROFIBUS-DP bus connector
is removed from the slave).
Clear I/O data
The output data received from the master will be
cleared to 0 and the input data will keep
unchanged when AH10PFBS-5A and the master
are offline (E.g. the PROFIBUS-DP bus connector
is removed from the slave).
8. Download the configuration data after configuration of the data is over.
After the connection between the master and AH10PFBS-5A is made and the NET light of
AH10PFBS-5A is green, it indicates that the communication between AH10PFBS-5A and
the PROFIBUS-DP master is normal. Otherwise, shoot the trouble according to the
instruction in chapter 8.