AH500 Module Manual
14-30
Setting of AH04DA-5A
After configuring AH04DA-5A, refer to Figure 4 for the related parameters setting.
Figure 4
Explanation of the options above
Name Setting Explanation
rack 0x01
The number of the rack where the I/O module is
(Rack number ranges from 1 to 8, 1 represents
the main rack, 2~8 stand for extension racks and
the slot number is 0~11.)
slot 0x03
The number of the slot on the rack where the I/O
module is. (Rack number ranges from 1 to 8, 1
represents the main rack, 2~8 stand for
extension racks and the slot number is 0~11).
CH0~CH3 output
mode
disable
-10V~+10V
0V~10V
5V~+5V
0V~+5V
1V~+5V
0mA~20mA
4mA~20mA
The output channel mode of AH04DA-5A is
disabled by default.
Mode: disable
Mode: -10V~+10V
Mode: 0V~10V
Mode: -5V~+5V
Mode: 0V~+5V
Mode: 1V~+5V
Mode: 0mA~20mA
Mode: 4mA~20mA
CH0~CH3 output
hold
disable/enable
Output hold options
Enable: When the master PLC stops running, the
output value of the output channel of the
module remains the same as that before
the master PLC stops running.
Disable: The output value of the output channel
of the module is 0 when the master
PLC stops running.