Chapter 14 Remote I/O Communication Module AHRTU-PFBS
14-31
Setting of AH08DA-5B
After configuring AH08DA-5B, refer to Figure 5 for the related parameters setting.
Figure 5
Explanation of the options above
Name
Setting
Explanation
rack 0x01
The number of the rack where the I/O module are
placed (Rack number is 1~8, 1 represents the
main rack, 2~8 are extension racks and the slot
number is 0~11.)
slot 0x04
The number of the slot on the rack where the I/O
module is. (Rack number is 1~8, 1 represents the
main rack, 2~8 are extension racks and the slot
number is 0~11).
CH0~CH7 output
mode
disable
-10V~+10V
0V~10V
5V~+5V
0V~+5V
1V~+5V
The output channel mode of AH08DA-5B is
disabled by default.
Mode: disable
Mode: -10V~+10V
Mode: 0V~10V
Mode: -5V~+5V
Mode: 0V~+5V
Mode: 1V~+5V
CH0~CH7 output
hold
disable/enable
Output hold options
Enable: the output of other I/O modules of
AHRTU-PFBS-5A is held when some I/O module
has a fault and the master is disconnected or
stops running.
Disable: the output of other I/O modules of
AHRTU-PFBS-5A is cleared to 0 when some I/O
module has a fault and the master is
disconnected or stops running.