AH500 Module Manual
14-32
Setting of AH08DA-5C
After configuring AH08DA-5C, refer to Figure 6 for the related parameters setting.
Figure 6
Explanation of the options above
Name Setting Explanation
rack 0x01
The number of the rack where the I/O module is
(Rack number ranges from 1 to 8, 1 represents
the main rack, 2~8 stand for extension racks and
the slot number is 0~11.)
slot 0x05
The number of the slot on the rack where the I/O
module is. (Rack number ranges from 1 to 8, 1
represents the main rack, 2~8 stand for
extension racks and the slot number is 0~11).
CH0~CH7 output
mode
disable
0mA~20mA
4mA~20mA
The output channel mode of AH08DA-5C is
disabled by default.
Mode: disable
Mode: 0mA~20mA
Mode: 4mA~20mA
CH0~CH7 output
hold
disable/enable
Output hold options:
Enable: the output of other I/O modules of
AHRTU-PFBS-5A is held when some I/O module
has a fault and the master is disconnected or
stops running.
Disable: the output of other I/O module
s of
AHRTU-PFBS-5A is cleared to 0 when some I/O
module has a fault and the master is
disconnected or stops running.