Chapter 14 Remote I/O Communication Module AHRTU-PFBS
14-33
Setting of AH06XA-5A
After configuring AH06XA-5A, refer to Figure 7 for the related parameters setting.
Figure 7
Explanation of the options above
Name Setting Explanation
rack 0x01
The number of the rack where the I/O module is
(Rack number ranges from 1 to 8, 1 represents
the main rack, 2~8 stand for extension racks and
the slot number is 0~11.)
slot 0x06
The number of the slot on the rack where the I/O
module is. (Rack number ranges from 1 to 8, 1
represents the main rack, 2~8 stand for
extension racks and the slot number is 0~11).
CH0~CH3 Input
mode
disable
-10V~+10V
0V~10V
5V~+5V
0V~+5V
1V~+5V
0mA~20mA
4mA~20mA
+20mA~-20mA
The input channel mode of AH06XA-5A is
disabled by default.
Mode: disable
Mode: -10V~+10V
Mode: 0V~10V
Mode: -5V~+5V
Mode: 0V~+5V
Mode: 1V~+5V
Mode: 0mA~20mA
Mode: 4mA~20mA
Mode: +20mA~-20mA
CH0~CH1 output
mode
-10V~+10V
0V~10V
5V~+5V
0V~+5V
The output channel mode of AH06XA-5A is
disabled by default.
Mode: disable
Mode: -10V~+10V
Mode: 0V~10V