AH500 Module Manual
14-82
After the master establishes the communication with the slave, the data in registers D in the master
PLC and the state of the modules connected to AHRTU-PFBS-5A are shown as the following table.
Register in
master PLC
Value
Data
transmitted
through
PROFIBUS
Devices connected to
AHRTU-PFBS-5A
Value/ State
D6000
bit0~bit7
15
Y0.0~Y0.7 of the 1
st
16AP on the main
rack
Y0.0~Y0.3 ON
and others
OFF
D6001
bit0~bit7
15
Y0.0~Y0.7 of the 2
nd
16AP on the main
rack
Y0.0~Y0.3 ON
and others
OFF
D6004 16000
Digital value that
channel 0 in 08DA
corresponds to
Channel 0
outputs 5V
voltage
D6005 16000
Digital value that
channel 1 in 08DA
corresponds to
Channel 1
outputs 5V
voltage
D6006 16000
Digital value that
channel 2 in 08DA
corresponds to
Channel 2
outputs 5V
voltage
D6007 16000
Digital value that
channel 3 in 08DA
corresponds to
Channel 3
outputs 5V
voltage
D6012
bit0~bit7
15
Y0.0~Y0.7 of the 1
st
16AP on the
extension rack
Y0.0~Y0.3 ON
and others
OFF
D1000
bit0~bit7
15
X0.0~X0.7 of the 1
st
16AP on the main
rack
X0.0~X0.3 ON
and others
OFF
D1001
bit0~bit7
15
X0.0~X0.7 of the 2
nd
16AP on the main
rack
X0.0~X0.3 ON
and others
OFF
D1002 About 16000
Digital value that the
input channel 0 in
06XA corresponds to
Channel 0
inputs 5V
voltage
D1003 About 16000
Digital value that the
input channel 1 in
06XA corresponds to
Channel 1
inputs 5V
voltage
D1004 About 16000
Digital value that the
input channel 2 in
06XA corresponds to
Channel 2
inputs 5V
voltage
D1005 About 16000
Digital value that the
input channel 3 in
06XA corresponds to
Channel 3
inputs 5V
voltage
D1006
bit0~bit7
15
Y0.0~Y0.7 of the 1
st
16AP on the
extension rack
X0.0~X0.3 ON
and others
OFF

Table of Contents