Chapter 16 Remote I/O Module AHRTU-ETHN-5A
16-15
Name Description
IP Addressing
Mode
Mode of getting IP address
Static: Fixed IP address.
DHCP: DHCP server assigns the dynamic IP address.
BOOTP (default): BOOTP server assigns the dynamic IP address.
If DHCP or BOOTP is selected, you can make the setting through IP
manager in EIP Builder.
IP Address
Set an IP address; default: 192.168.1.3.
Netmask Address
Set the IP address for networkmask; default: 255.255.255.0
Gateway Address
Set the IP address for gateway; default: 192.168.1.1
Keep Alive Timer
Set the time for keeping connection alive. If the upper machine does not
send the packet to AHRTU-ETHN-5A within the set time, AHRTU-ETHN-5A
will automatically cut the connection with it.
Ethernet - Advance
The tab provides the setting of AHRTU-ETHN-5As advanced Ethernet functions including filter and
NTP.
Filter_IP address filter setting
The above page sets the filter function of network devices. Only the devices of which IP addresses
are in the set range are allowed to communicate with AHRTU-ETHN-5A. The packets sent by the
devices of which the IP addresses are out of the set range will be discarded. At most 16 groups of IP
address ranges can be set.
Steps for setting the function:
(1) Select Enable IP Address Filterand then double click one line of the following table to open
the IP Address Filter window.