AH500 Module Manual
16-28
Category
Error
code
7-segment
display
Explanation How to deal with
16#1003 -
Modify the IP
address when in
RUN state.
-
Firmware
error
16#1004 F7
Firmware update
failure
1. Check if the two ends of the
network are connected
properly.
2. Perform the firmware update
again.
16.7.2.2 I/O Module Error
Category
Error
code
7-segment
display
Explanation How to deal with
I/O module
configuration
error
16#2001 F9
Actually connected
I/O module is
different from that
configured in the
software.
1. Re-install I/O module
2. Repower ON
3. Re-download the
configuration.
Backplane
configuration
error
16#2002 F8
Actually connected
backplane is
different from that
configured in the
software.
1. Re-install the backplane
2. Repower ON
3. Re-download the
configuration.
Extension
backplane
offline
16#2003 FA
The connection
between the main
backplane and
extension
backplane are
disconnected.
1. Check if the cable connection
is normal.
2. Repower ON
16.7.2.3 Communication Error
Category
Error
code
7-segment
display
Explanation How to deal with
EtherNet/IP
communication
error
16#0106 -
Ownership
conflict
1. Check the scanner owner.
2. Modify the invalid scanner
setup.
3. Change the connection into
Multicast.
EtherNet/IP
communication
error
16#0113 -
Out of
connections
1. Check if the number of product
connections exceeds the limit.
2. Reduce the number of product
connections.
16#0100 -
I/O
connections
duplicated
1. Check if I/O connections have
been built in the system
configuration.
2. Change the connection type
into Listen Only.
16#0203 E3
I/O
connection
1. Check if the network cable
connection is normal.