Chapter 16 Remote I/O Module  AHRTU-ETHN-5A 
16-29 
Category 
Error 
code   
7-segment 
display 
Explanation  How to deal with 
2.  Check if the module is normal. 
3.  Raise the setting value of RPI.   
16#3001  E4 
offline   
Check if Ring network products 
are connected correctly. 
MODBUS TCP 
communication 
error 
16#5000  - 
Out of 
connections 
1.  Check if the number of 
product connections exceeds 
the limit. 
2.  Reduce the number of 
product connections. 
NTP 
communication 
error 
16#5001  - 
NTP Server 
connection 
failure 
1.  Check the setup for server 
connection. 
2.  Check if the system server 
exists. 
3.  Check if the wiring for 
connection of the server is 
proper.   
16#5002  - 
NTP time 
update 
failure 
connection is normal. 
2.  Check if the NTP parameter 
setup is correct. 
 
16.7.3  Indicator Status  
  MS/NS Indicator 
Indication  How to deal with 
LED OFF  LED OFF 
Check if the supply power works 
normally. 
red light blink 
alternately 
red light blink 
alternately 
No correction 
Green light ON  - 
finished. 
Red light ON  - 
CPU hardware error 
1. 
Check if the error indicator is OFF 
after re-installing the module after 
power OFF.   
2.  Replace the module and install 
the new module. Check if the 
error indicator is OFF.   
3.  Contact the local distributor.   
error 
Flash 
error 
- 
Green light blinks 
I/O connection is not 
made. 
No correction. 
Green light ON 
I/O 
been made. 
- 
Red light blinks 
I/O 
timeout 
1.  Check if the network cable 
connection is proper.   
2.  Check if the module is normal. 
3.  Raise the setting value of RPI 
Red light blinks
-  IP setup error 
Check if the IP address setup is 
legal. 
1.  Check if there are duplicated IP