2 Equipment Description
2.20 24 Vdc Fuse Protection
106 HPM High-Performance Process Manager Service R688
Honeywell December 2020
Right 7-Slot card file
Table 6 Right 7-Slot Card File Backpanel Fuse Protection lists the individual backpanel fuses and their
application for the Right 7-Slot card file. The fuse rating is 2 A for fuse locations F1 through F8.
Right 7-Slot Card File Backpanel Fuse Protection
When HPMM cards occupy the left two slots of a card file, fuse F2 is not in use. Fuse F1 on the
backpanel is used to supply 24 Vdc to the UCN Interface Module.
Table 6 Right 7-Slot Card File Backpanel Fuse Protection
Fuse
Rating
Protection Application
F1
2 A fast-action
Slot 9 IOP card and associated FTA
or
UCN Interface Module (24 Vdc) if HPMM exists in
card file
F2
2 A fast-action
Slot 10 IOP card and associated FTA
F3
2 A fast-action
Slot 11 IOP card and associated FTA
F4
2 A fast-action
Slot 12 IOP card and associated FTA
F5
2 A fast-action
Slot 13 IOP card and associated FTA
F6
2 A fast-action
Slot 14 IOP card and associated FTA
F7
2 A fast-action
Slot 15 IOP card and associated FTA
F8
2 A fast-action
HLAI Optical Coupler Module, U1