3 UCN Status Displays
3.4 Display Operation
R688 HPM High-Performance Process Manager Service 197
December 2020 Honeywell
CONTROL STATES display targets
The command targets at the bottom of the display in Figure 99 perform the functions defined in the
following table.
Table 27 UCN Status Display CONTROL STATES Target Selected
Target
Function
UCN FULL CONTROL
Changes the UCN’s control state to FULL. The command
is executed by selecting the ENTER target.
UCN BASIC CONTROL
Changes the UCN’s control state to BASIC. The command
is executed by selecting the ENTER target.
DEV FULL CONTROL
Changes the HPM’s control state to FULL. The command
is executed by selecting the ENTER target.
DEV BASIC CONTROL
Changes the HPM’s control state to BASIC. The command
is executed by selecting the ENTER target.
ALL DEVICES
Causes all the UCN devices to be affected by a control
state change.
CANCEL
Clears the UCN FULL CONTROL, UCN BASIC
CONTROL, DEV FULL CONTROL, DEV BASIC
CONTROL, ALL DEVICES, and ENTER command targets
from the display.
ENTER
The ENTER target must be selected for the chosen
CONTROL STATES function to be executed.