7 IOP Calibration Procedures
7.6 Redundant HLAI IOP Calibration Procedure
R688 HPM High-Performance Process Manager Service 449
December 2020 Honeywell
Calibration connections
The following figure is an illustration of the redundant HLAI FTA connections necessary to calibrate an
HLAI IOP.
Figure 217 Redundant HLAI Calibration Connections