EasyManua.ls Logo

Honeywell HPM

Honeywell HPM
498 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Equipment Description
2.27 EUCN Cable System
R688 HPM High-Performance Process Manager Service 149
December 2020 Honeywell
Table 16 ENB Cable Faults
Error scenario
UCN COMM STATUS
UCN CABLE
STATUS/FTE
CABLE STATUS
$FTESTS2
displays
(ENB with cable
faults)
$FTESTS2
displays
(all other
EUCN nodes)
No FTE cable
problems
A
SIL
B
SIL
A
NSY
B
NSY
OK/OK
UCN:
OK/BACKUP
LCN: OK/BACKUP
FTE composite status
A->A
A->B
B->A
B->B
OK
OK
OK
OK
If FTE cable A on
a Primary ENB
node has a
problem
A
SIL
B
SIL
A
NSY
B
NSY
FAIL/FAIL
UCN:
OK/BACKUP
LCN: OK/BACKUP
*
FTE composite status
A->A
A->B
B->A
B->B
SIL
SIL
SIL
OK
If FTE cable B on
a Primary ENB
node has a
problem
A
SIL
B
SIL
A
NSY
B
NSY
FAIL/FAIL
UCN:
OK/BACKUP
LCN: OK/BACKUP
*
FTE composite status
A->A
A->B
B->A
B->B
OK
SIL
SIL
SIL
If both FTE cable
A and FTE cable
B on a primary
ENB have a
problem
Primary fails,
Secondary takes
over as the
primary
A
SIL
B
SIL
A
NSY
B
NSY
OK/OK
UCN:
OFFNET/OK
LCN:
FAIL/WARNING
*
[1]
*
[1]
FTE composite status
A->A
A->B
B->A
B->B
OK
OK
OK
OK
If both FTE cable
A and FTE cable
B on a secondary
ENB have a
problem
A
SIL
B
SIL
A
NSY
B
NSY
FAIL/OK
UCN:
OK/BACKUP
LCN: OK/SEVERE
*
*
FTE composite status
A->A
A->A
A->A
B->B
OK
OK
OK
OK

Table of Contents