EasyManua.ls Logo

Honeywell HPM - SDI Interface Configuration; Figure 11 Serial Device Interface Interconnections

Honeywell HPM
498 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Equipment Description
2.10 Serial Device Interface IOP (SDI)
64 HPM High-Performance Process Manager Service R688
Honeywell December 2020
SDI interface configuration
The following figure illustrates a typical Serial Device Interface configuration.
Figure 11 Serial Device Interface Interconnections
A-Size
Card File
Model
MU-TLPA02
Power
Adapter
UNIT 0 UNIT 1
Model MU-PSDX02
Serial Device Interface
IOP
Model
MU-TSDT02
Serial Device
Interface
FTA
A-Size
Model
MU-TSDM02
Serial Device
Interface
FTA
Toledo Weigh
Cell Model
8142-2089
or
8142-2189
Customer Supplied
EIA-232 (RS-232) Interface Cable
[15 m (50 ft) Maximum Length]
Model
MU-MASX02
Manual/Auto
Station
Device 1
Model
MU-MASX02
Manual/Auto
Station
Device 2
Model
MU-MASX02
Manual/Auto
Station
Device 3
Model
MU-MASX02
Manual/Auto
Station
Device 4
EIA-422/485 (RS-422/485) Interface Cable
[305 m (1000 ft) Maximum Length]
See note.
Model MU-KLAMxx Internal Cabinet Cable
or
Model MU-KLXxxx External Cabinet Cable
[305 meters (1000 feet) Maximum Length]
Model MU-KFTAxx FTA Cable
[50 meters (164 feet) Maximum Length]
5007
Note:
Total maximum length can be up to 1200 meters
(4000 feet) when using the appropriate type of cable.